Fire protection – automatic smoke extraction



          Automatic smoke outlet systems

                                                                         smoke evacuation
                                                                         blower with type
                 fresh air  ap                                           approval





                                                                         smoke evacuation
                                                                         damper with type
                                                                         approval








                                                                         smoke evacuation
                                                                         damper with type
                                                                         approval






                                  ceiling-mounted
                                  smoke detector                         safety
                                  DRM 3.3-X                              network
                                   push-button alarm
                                   DKM 3.3








                                                      STG 1.2
                                                      control units

                                                     automation station
                                                     i.a.w. EN 61508


          Operating mode:                                  Requirements:
          This sketch shows you the interaction of detectors and actuators  •  DIN 18232 – structural fire protection, smoke / heat removal
          in order to efficiently avoid the spreading of fire and smoke    •   Number and arrangement of the smoke detectors is
          by means of a RLT system which is installed in the building.  specified in VDE 0833
          In case a smoke detector which has been installed in the fire  •   Requires its own circuit with its own separately
          section sets off an alarm, the designated smoke extracting flap  signed fuse protection
          of the automation station triggered by the STG 1.2 control unit  •  Smoke detectors according to EN 54-7
          will open and the smoke extracting ventilator will be turned on.  •   Preservation of the functionality of the wires
          Other smoke extraction flaps are closed in order to concentrate  for a min. of 30 min. according to DIN 4102-12
          the extract air volume on one smoke zone.        •  Signalling of contamination
                                                           •  Signalling of system failure
                                                           •  Manual overmodulation is possible
                                                           •  Smoke protection areas may not exceed fire areas
                                                           Note: Subject to change.
                                                           The local rules and regulations apply.