Page 149 - OP_Katalog_EN
P. 149

Control, smoke alarm, manual alarms

               (analog technology)
                                                                            Type              Item no. ADG Euro  /  pc.

                             Optical smoke detector                         DRM SOC-E3N-YBN   104723  04  see our
                             for indoor use for early detection of smoldering fire and fire              current
                             with smoke development. The detector operates according                    price list
                             to the scattered light principle. Delivery including mounting
                             base. Light transmitters and receivers are arranged in the
                             measuring chamber in a way that the luminous beam of the
                             transmitter cannot hit the receiver directly. Only the light which is
                             scattered from floating particles (Tyndall effect) reaches the receiver
                             and is converted into an electrical signal. The red LED flashes to
                             indicate contamination (service) and lights up permanently
                             in the event of an alarm. The detector is operated by the control
                             device ABAV-S (Data sheet no. 43102) which also supplies the
                             measuring voltage, alarm current: 40 mA
                             Permiss. amb. temperature: -10 – 50 °C
                             VdS test certificate: G217088
                             Data sheet no. 40105

                             Optical smoke detector                         DRM SOC-E3N-YBO   104724  04
                             with alarm relay with potential-free contact.
                             Delivery including mounting base. For indoor use for early
                             detection of smoldering fire and fire with smoke development.
                             The detector operates according to the scattered light principle.
                             Light transmitters and receivers are arranged in the measuring
                             chamber in a way that the luminous beam of the transmitter
                             cannot hit the receiver directly. Only the light which is scattered
                             from floating particles (Tyndall effect) reaches the receiver and
                             is converted into an electrical signal.
                             The red LED flashes to indicate contamination (service) and
                             lights up permanently in the event of an alarm. Relay contact,
                             loadable with 24 V / 1 A .
                             Permiss. amb. temperature: -10 – 50 °C
                             VdS test certificate: G217088
                             Data sheet no. 40202

                             Thermodifferential alarm 24 V DC               DRM DCD-AE3-YBN   104725  04
                             as fire detector for installation at ceilings.
                             Responds to a fast temperature rise or to the exceeding
                             of a fixed temperature limit value. LED display and contact output
                             via controller ABAV-S. Delivery including mounting base.
                             The fire detector is used in areas where smoke detectors would
                             cause false alarms due to environmental conditions like smoke,
                             steam or dust. The speed of the temperature rise is defined
                             according to EN 54 class A1R. (static maximal construction
                             temperature 50 °C in normal operation). The upper temperature
                             limit value is set fixed to 57 °C ± 3 K. The thermodifferential
                             alarm runs with the controller ABAV-S which also supplies
                             the voltage of 24 V DC.
                             Alarm current consumption:    40 mA at 24 V DC
                             Permiss. amb. temperature:    -10 – 50 °C no icing
                             Dimensions with base:   100 x 46 mm (ø x H)
                             Data sheet no. 43502

                                                                                                                      FIRE PROTECTION









               For our current prices see www.oppermann-regelgeraete.de/en/downloads/catalogue-1   Catalog 2024  |  Fire protection  |  149