Page 143 - OP_Katalog_EN
P. 143

KRM-X® Duct smoke detectors
                                                                            Type              Item no. ADG Euro  /  pc.

                             DIBt-version – for control of fire and smoke protection flaps

                             Duct smoke detector  230 V AC                  KRM-X-1-DZ 0.16   104526  42  see our
                             Duct smoke detector  230 V AC                  KRM-X-1-DZ 0.6    104525  42  current
                                                                                                        price list
                             Duct smoke detector  230 V AC MOD              KRM-X-1-DZ-MOD 0.16  104534  42
                             Duct smoke detector  230 V AC MOD              KRM-X-1-DZ-MOD 0.6  104533  42

                             Duct smoke detector  230 V AC BAC              KRM-X-1-DZ-BAC 0.16  104530  42
                             Duct smoke detector  230 V AC BAC              KRM-X-1-DZ-BAC 0.6  104529  42

                             Duct smoke detector  24 V AC / DC              KRM-X-2-DZ 0.16   104546  42
                             Duct smoke detector  24 V AC / DC              KRM-X-2-DZ 0.6    104545  42

                             Duct smoke detector  24 V AC / DC              KRM-X-2-DZ-MOD 0.16 104554  42
                             Duct smoke detector  24 V AC / DC              KRM-X-2-DZ-MOD 0.6  104553  42

                             Duct smoke detector  24 V AC / DC              KRM-X-2-DZ-BAC 0.16  104550  42
                             Duct smoke detector  24 V AC / DC              KRM-X-2-DZ-BAC 0.6  104549  42

                             Versions 0.16 incl. 0.16 m LKR-X sensor tube; fits all duct
                             cross-sections*.
                             Versions 0. 6 incl. 0.6 m LKR-X sensor tube (optionally also available
                             with 1.5 m or 3.0 m)

                             Detector type:     RM 3.3-X (ALN-E) scattered light detector
                             Supply voltage:      KRM-X-1-DZ / KRM-X-1-DZ-MOD /
                                                 KRM-X-1-DZ-BAC:
                                                230 V AC ± 10 %, 50 / 60 Hz
                             Supply voltage:      KRM-X-2-DZ / KRM-X-2-DZ-MOD /    Oppermann
                                                                                  Regelgeräte
                                                                                   GmbH
                                                KRM-X-2-DZ-BAC:                    Z-78.6-249
                                                24 V AC (16 – 27.6 V AC) or       VdS
                                                24 V DC (21.6 – 27.6 V DC)
                             Nominal current:     KRM-X-1-DZ / KRM-X-1-DZ-MOD /
                                                KRM-X-1-DZ-BAC: 30 mA
                                                  KRM-X-2-DZ / KRM-X-2-DZ-MOD /
                                                KRM-X-2-DZ-BAC: 120 mA
                             Operating temperature:    -20°C – 50°C
                             Protection type:    IP 65
                             Approvals / Certifications:      DIBt certification
                                                VdS approval,
                                                DIN EN 54-27
                             Permissible flow velocity:   1 – 20 m / s
                             Dimensions:        ca. 271 x 172 x 85 mm (L x W x H)
                             Cable glands:      3 x M16
                             Data sheet no. 41351
                             VdS approval G219046 / G219053
                             DIBt approval no. Z-78.6-249
                             Modbus protocol KRM-X … -DZ-MOD
                             BACnet protocol KRM-X … -DZ-BAC

                             *  The 0.16 m long LKR-X TurboTube sampling tube is also suitable for larger channels and approved. There are no restrictions on the maximum
                              channel width / height / diameter. In conjunction with console KS-KRM-X®, channels to > = 80 mm diameter can be monitored. The longer LKR-Xs
                              can be shorted when required.
                             Note: For the control of fire and smoke protection flaps building authority approved smoke detectors with general   FIRE PROTECTION
                             technical approval by the DIBt (German Institute for Building Technology) are required (see MVV TB for Germany).




               For our current prices see www.oppermann-regelgeraete.de/en/downloads/catalogue-1   Catalog 2024  |  Fire protection  |  143
   138   139   140   141   142   143   144   145   146   147   148