Accessories for KRM-X® duct smoke detector
                                                                      Type              Item no. ADG Euro  /  pc.

                       NT* power supply unit                          NT01 - 24V-AC      103472  04   see our
                       Basic power supply unit IP 20. DIBt certification for use with    NT02 - 24V-DC  103473  04  current
                       KRM-X-2-DZ / KRM-X-2-DZ-MOD / KRM-X-2-DZ-BAC (DIBt designs)                 price list
                       has been applied for. Required for a safe 24 V AC or 24 C  DC power
                       supply. An NT01 unit can supply up to 5 and an NT02 up to
                       3 KRM®/KRM-X® detectors.
                       Please specify required type / voltage rating when ordering.
                       Supply voltage:    230 V AC +10 % / -15 %; 50 – 60 Hz
                       Power draw:      NT01: < 30 VAC; NT02: < 25 W
                       Output power: NT01:    max. 24 VA (24 V AC);
                       NT02:            max. 20 W (24 V DC)
                       LED display:     operation (green)
                       Housing:         PC, gray with clear cover, IP 20
                       Permiss. amb.
                       temperature:     -20 – 50 °C
                       Dimensions:      ca. 125 x 125 x 60 mm (W x H x D)
                       Weight:          NT01: ca. 0.8 kg; NT02: ca. 0.4 kg

                       Replacement safety fuses
                       for NT01-24V-AC
                       primary side, 160 mA rating, slow-acting       SI-0.16A-T         104733  04
                       secondary side, 1.25 A rating, slow-acting     SI-1.25A-T         104124  04

                       for NT02-24V-DC
                       primary side 0.63 A rating, slow-acting        SI-0.63A-T         104125  04
                       Data sheet no. 41305

                       Display unit* for Modbus-compatible KRM-X      AZE 1.2            100050  04
                       For connecting and displaying the operating states of up to
                       99 Modbus-compatible type KRM-X® duct smoke detectors. This
                       display shows and evaluates occurrences of smoke, contamination,
                       and malfunction and monitors cables for cable breakage and short
                       circuits. Output information is shown in plain text on an LCD display
                       or signaled by LEDs. Messages are transmitted via potential-free
                       contacts or an RS485 interface and forwarded to building auto-
                       mation systems. The status of each detector can be queried using
                       a keyboard. The housing has a snap-on base for mounting on a
                       mounting rail in a control cabinet.
                       Dimensions: ca. 160 x 90 x 50 mm (W x H x D), Protection type IP 20
                       Permissible ambient temperature 0 – 50 °C
                       Data sheet no. 43105

                       *also compatible with KRM