Page 108 - OP_Katalog_EN
P. 108
OPP-ROOM® I / O module
Type Item no. ADG Euro / pc.
OPP-ROOM® I / O module see our
For connecting external analog portable devices and room current
sensors, conversion to Modbus or BACnet. price list
Display not possible.
Supply voltage: 24 V AC / DC
Permiss. amb. cond.: -30 – 70 °C, 0 – 95 % RH
(non-condensing)
Housing: Plastic (ABS); IP20,
White similar to RAL 9010,
wall-mounted
Dimensions: 86 x 120 x 25 mm (L x W x D)
Terminals: Screw terminals 0.05 – 1.5 mm2
Version IO4:
Inputs: 2 x switching input
(closer, potential-free)
Outputs: 2 x DO digital outputs –
only with 24 V AC supply voltage
Modbus transmitter (Modbus RTU) IO-MOD-R-IO4 103916 23
BACnet transmitter (MS / TP) IO-BAC-R-IO4 103914 23
Version IO9:
Inputs: 2 x switching input
(closer, potential-free)
2 x analog input
(0 – 50 kΩ, e.g. for NTC)
Outputs: 3 x 0 – 10 V DC
2 x DO digital outputs –
only with 24 V AC supply voltage
Modbus transmitter (Modbus RTU) IO-MOD-R-IO9 103915 23
BACnet transmitter (MS / TP) IO-BAC-R-IO9 103913 23
Data sheet no. 20550
BACnet protocol OPP-ROOM
(downloadable from our website)
OPP-ROOM® USB configuration cable CAB-02 103918 23
For connecting active OPP-ROOM® transmitters with the PC.
Needed to configure the transmitter with OR-C software.
108 | Catalog 2024 | Sensors For our current prices see www.oppermann-regelgeraete.de/en/downloads/catalogue-1