Page 91 - OP_Katalog_EN
P. 91

Safety temperature limiter
                                                                            Type              Item no. ADG Euro  /  pc.

                             Electromechanical safety temperature limiter   STB-01            104217  02  see our
                             For use in heat generators and other HVAC applications.                     current
                             Intrinsically safe design. Rupture of the capillary tube causes the         price list
                             contact to open. After a temperature-triggered shutdown the
                             sensor tube must be allowed to cool down by ca. 25 ± 5 K before
                             manual reset becomes possible.
                             There are various installation options: direct mounting on the
                             immersion sleeve, raised mounting, mounting on the pipe or in the
                             air duct.                                                                                SENSORS
                             If it is to be installed directly on the immersion sleeve, the safety
                             temperature limiter (STB) / temperature monitor (TW) must be
                             fastened on the immersion sleeve fitting. Immersion sleeves and
                             mounting hardware are not included in the scope of delivery.
                             Accessories are listed on pages 93 and 94. Immersion sleeves
                             TH should be selected from those listed under Accessories STB / TW
                             to ensure conformity to the requirements of EN 14597.

                             Protection type:    IP 66
                             Setting range:      90 – 110 °C
                             Length of capillary tube:   approx. 1 m
                             Electrical changeover contact:
                             Break contact       2,5 ... 10 A / 40 ... 250 V AC
                             Closing contact     0,5 A / 40 ... 250 V AC
                             Connection:         screw terminals
                             Cable grommet:      M20
                             Permiss. amb. cond.:     0 – 70 °C, 0 – 95 % RH
                                                 (non-condensing)
                             Dimensions (W x H x D):   approx. 70 x 110 x 70 mm
                             Data sheet no. 20680







 Specification type HWS
 for very large fans, from approx. 22 kW


































               For our current prices see www.oppermann-regelgeraete.de/en/downloads/catalogue-1   Catalog 2024  |  Sensors  |  91