Page 48 - OP_Katalog_EN
P. 48

OPP-SENS® Duct enthalpy

          humidity temperature sensors
                                                                      Type              Item no. ADG Euro  /  pc.

                       OPP-SENS®Duct humidity temperature sensor (enthalpy)  HTx-xxx-I-...  see    see our
                       For measuring enthalpy temperature in air ducts.                 following   current
                       The optional display enables you to configure the transmitter such   page   price list
                       that it indicates and outputs absolute or relative humidity or the
                       mixture ratio instead of enthalpy. The absolute air pressure can also
                       be set via the display.
                       Display and control unit with autoadapt and capacitive
                       button (option). This enables the NFC function, allowing easy
                       sensor parameterization via a smartphone.
                       5-point calibration: linear interpolation of the output
                       curve over 5 user-defined points.
                       10 offset points: linear shift of characteristic curve the output
                       signal via 10-level rotary switch.
                       Captive lid with 8-way positioning.

                       10 measurement ranges can be set using the rotary switch:
                       0 – 50 kJ / kg   0 – 80 kJ / kg   0 – 100 kJ / kg*  0 – 200 kJ / kg
                       0 – 400 kJ / kg   0 – 1000 kJ / kg   -50 – 50 kJ / kg   -50 – 200 kJ / kg
                       -50 – 400 kJ / kg  -50 – 1000 kJ / kg  *factory settings
                       Measuring range
                       temperature:             Factory settings -50 to 50 °C,
                                              with adjustable optional display
                                              between -50 and 100 °C
                       Supply voltage:
                       2-wire                 24 V DC
                       3-wire / Modbus / BACnet   24 V AC / DC
                       Output:
                       2-wire                 4 – 20 mA
                       3-wire                 0 – 10 V or 4 – 20 mA
                                              switchable or bus
                       Margins of error:
                       Humidity               ± 3 % RH at 25 °C for 20 – 80 % RH
                       Temperature            ± 0.5 °C for 0 – 65 °C
                       Permiss.
                       ambient conditions:      -20 – 70 °C, 0 – 95 % RH
                                              (non-condensing)
                       Permiss. media temp.:    -40 – 100 °C
                       Nominal diameter:      Stainless steel sleeve ø 10 mm
                       Mounting:              air duct mounting flange F-10
                                              (included)
                       Housing:               IP 65 including seal,
                                              Plastic gray / yellow
                       Terminals:             Spring terminals 0.2 – 1.5 mm2
                       Cable gland:           M16






















          48  |  Catalog 2024  |  Sensors   For our current prices see www.oppermann-regelgeraete.de/en/downloads/catalogue-1