OPP-SENS® External relative
humidity sensors
Type Item no. ADG Euro / pc.
OPP-SENS® External humidity sensor H-...-OUT see our
(relative humidity) current
For the measurement of relative humidity outside. price list
Display and control unit with autoadapt and capacitive
button (option). This enables the NFC function, allowing easy
sensor parameterization via a smartphone.
5-point calibration: linear interpolation of the output
curve over 5 user-defined points.
10 offset points: linear shift of characteristic curve the output
signal via 10-level rotary switch.
Captive lid with 8-way positioning.
Output humidity: 0 – 100 % RH linear
Supply voltage: 24 V AC / DC
Output: 0 – 10 V or 4 – 20 mA
switchable
Margin of error:
Humidity ± 3 % RH at 25 °C
for 20 – 80 % RH
Permiss. amb. cond.: -20 – 70 °C, 0 – 95 % RH
(non-condensing)
Housing: IP 65 including seal,
Plastic gray / yellow
Terminals: Spring terminals 0.2 – 1.5 mm2
Cable gland: M16
Current / Voltage transmitter
(3-wire, 0 – 10 V / 4 – 20 mA switchable)
without display* H-T-OUT 104103 22
with display and NFC interface H-T-OUT-D-NFC 105158 22
Data sheet no. 20916
* For programming/assigning addresses and 5P calibration, a display must be used at least once.