Page 62 - OP_Katalog_EN
P. 62

Differential air pressure transmitter
                                                                      Type              Item no. ADG Euro  /  pc.

                       Differential pressure transmitter              DDS-AR984xx                  see our
                       with automatic zero point adjustment                                        current
                       1 or 2 measuring ranges (Code AR)                                           price list
                       Complete unit (without fastening angles)
                       for vertical installation, consisting of:
                       Differential pressure monitor and clima-set straight type 6555.

                       Output signal:      switchable root extracting / linear
                       Output:               0 – 10 V or 4 – 20 mA adjustable
                                           (3-wire) with additional npn open
                                           collector switching output
                       Dimensions:           ø 85 x 58 mm (L x W),
                       protection class:    IP 54
                       Voltage supply:     18 – 30 V AC, 16 – 32 V DC (3-wire)
                       Uncertainty (total error disregarding long-time and
                       temperature influences):    ±1% of full scale, min. ±1 Pa
                       Permiss. amb. cond.:      -10 – 50 °C, 0 – 95 % RH
                                           (non-condensing)
                       Data sheet no. 13252
                       without display                                DDS-AR984.5.….3.K.0  s. table  12
                       with display                                   DDS-AR984.5.….3.K.1  on   12
                                                                      … = Code for pressure  request
                                                                      range
                                                                      see sample table
                                                                      below

                        Type                    Item no.  Measuring   Measuring    Overpress.   Temperature
                        (Pressure range)                  range 1     range 2      safety      error
                        DDS-AR984.5.E.3.K.0     102799    ± 25 Pa     -            60 kPa      ≤ ±  3% v. EW
                        DDS-AR984.5.X.3.K.0     103241    ± 50 Pa     -            60 kPa      ≤ ±  2 % v. EW
                        DDS-AR984.5.W.3.K.0     103240    ± 100 Pa    -            60 kPa      ≤ ±  1,5 % v. EW
                        DDS-AR984.5.0.3.K.0     103238    0 – 25 Pa   0 – 50 Pa    60 kPa      ≤ ±  3 % v. EW
                        DDS-AR984.5.1.3.K.0     103229    0 – 50 Pa   0 – 100 Pa   60 kPa      ≤ ±  2 % v. EW
                        DDS-AR984.5.2.3.K.0     103246    0 – 100 Pa  0 – 250 Pa   60 kPa      ≤ ±  2,5 % v. EW
                        DDS-AR984.5.3.3.K.0     103239    0 – 250 Pa  0 – 500 Pa   75 kPa      ≤ ±  1,5 % v. EW
                        DDS-AR984.5.4.3.K.0     103143    0 – 500 Pa  0 – 1,000 Pa  75 kPa     ≤ ±  1% v. EW
                        DDS-AR984.5.5.3.K.0     103245    0 – 1 kPa   0 – 2,5 kPa  85 kPa      ≤ ±  1% v. EW
                        DDS-AR984.5.7.3.K.0     103244    0 – 5 kPa   0 – 10 kPa   135 kPa     ≤ ±  1% v. EW
                        DDS-AR984.5.9.3.K.0     103243    0 – 25 kPa  0 – 50 kPa   200 kPa     ≤ ±  1% v. EW
                        DDS-AR984.5.B.3.K.0     103242    0 – 100 kPa  0 – 250 kPa  400 kPa    ≤ ±  1% v. EW
                        DDS-AR984.5.….3.K.1  with display, technical information as above.



























          62  |  Catalog 2024  |  Sensors   For our current prices see www.oppermann-regelgeraete.de/en/downloads/catalogue-1
   57   58   59   60   61   62   63   64   65   66   67